A legionella test shows whether legionella have proliferated in the hot water. For private households, a self-test kit sent to a laboratory provides an initial indication. A legally required examination in Germany, however, requires sampling by an accredited and approved testing body. This comparison shows which of the three testing routes is suitable for what, what they roughly cost, and what to do in case of an abnormal result.
Key facts at a glance
Options include self-test kits submitted to a lab, on-site rapid tests, and professional sampling with laboratory analysis.
For a mandatory German inspection, the examination and sampling must be performed by an accredited and approved testing body — a self-submitted water sample does not suffice.
The technical action value in the German Drinking Water Ordinance is 100 colony-forming units (CFU) per 100 milliliters.
For rented buildings with a large hot-water system subject to mandatory testing, an inspection is required in Germany at least every three years.
While a result is being clarified, certified terminal sterile filters on the shower can retain legionella. They are not a substitute for remediation.
So the crucial question is not just: „How quickly will I get a result?“ A single measurement from your own bathroom serves a different purpose than an examination of an entire hot-water system. Those who know the differences can choose a test suited to their situation, instead of deriving too much reassurance from an inconspicuous rapid result or expecting a building inspection as a mere first indication.
What does a Legionella test actually measure?
A laboratory culture determines how many viable Legionella are detectable in a water sample; the result is usually given as colony-forming units, CFU, per 100 milliliters. Antigen rapid tests, by contrast, provide a detection but not necessarily a quantitative measurement. The focus is mainly on hot water: Legionella can multiply in drinking-water installations at temperatures of roughly 25 to 45 °C. If water stands for a long time in rarely used pipes, this further promotes growth. A report initially describes the sampled location and the time of collection. For the assessment of an entire system, it is therefore also important, where and how the sample was taken.
Why is the hot water tested and not the drinking glass?
The relevant transmission route is inhaling finely dispersed water droplets, so-called aerosols, for example when showering. Drinking tap water, on the other hand, is not the typical route of infection for Legionella. For older people as well as for people with weakened immune systems or certain pre-existing conditions, a possible exposure must be taken particularly seriously. That does not mean that tap water is inherently unsafe: in Germany and Austria it is strictly monitored. However, Legionella can only within the household plumbing vermehren, etwa wenn Warmwasser nicht ausreichend warm gehalten wird oder Leitungsabschnitte kaum durchströmt werden. Ein Test am Wasserwerk würde dieses Problem im eigenen Gebäude daher nicht beantworten.
Was bedeutet der MaĂźnahmenwert von 100 KBE/100 ml?
In Deutschland nennt die Trinkwasserverordnung für Legionellen einen technischen Maßnahmenwert von 100 KBE pro 100 Milliliter. Er ist kein Wert, unterhalb dessen unter allen Umständen jedes Gesundheitsrisiko ausgeschlossen wäre. Wird der technische Maßnahmenwert bei einer vorgeschriebenen Untersuchung erreicht oder überschritten, löst das festgelegte Melde- und Handlungspflichten aus. Die Untersuchungsstelle informiert das zuständige Gesundheitsamt; auch der Betreiber der Anlage muss seinen Pflichten nachkommen und die Ursache untersuchen lassen. Wie dringend einzelne Schutzmaßnahmen sind, hängt vom Befund und der Situation im Gebäude ab. Für einen selbst genommenen Test gilt diese amtliche Einordnung nicht automatisch: Seine Probe wurde nicht im vorgeschriebenen Untersuchungsverfahren gewonnen.
Which legionella tests are there and how good are they?
Three approaches are particularly common: a self-test kit whose sample you send to a laboratory, a rapid test performed by professionals on site, and sampling carried out by an accredited testing facility followed by laboratory analysis. All can provide information, but they answer different questions. The self-test usually examines a single selected tap. The rapid test quickly provides a preliminary overview. For the statutory testing obligation in Germany, however, the third route is required: sampling and analysis must be carried out by an accredited testing facility.
Self-test kit with laboratory submission
With a self-test, you take water from a tap according to the instructions and send the sample to a laboratory. It usually takes about seven to ten days to receive a result; the actual duration depends, among other things, on shipping and the lab's processing. Such kits typically cost around €50 in stores. For a private household this is a useful first indication, for example if a shower hasn't been used for a long time and you want to assess the condition at that location.
The limitation lies in the sampling: timing, handling, transport and the choice of tap all influence what the sample indicates. A normal value at one faucet does not automatically describe all pipe runs. Conversely, an abnormal result should be professionally interpreted rather than being taken to represent the entire building. For landlords with a statutory inspection obligation, a self-collected sample does not replace the required testing—even if the sent-in sample is subsequently analyzed in the laboratory.
On-site rapid test
A rapid test can give professionals an initial indication within minutes to hours. This is helpful, for example, when they need to quickly decide during a technical inspection which areas should be examined more closely. However, the term covers different test principles and detection ranges. Some antigen rapid tests detect only Legionella pneumophila of serogroup 1. This serogroup is significant for illnesses, but not the only relevant Legionella group. A negative result in such a test therefore does not mean that no other Legionella are present in the system.
Its strength is speed, not legal evidentiary value. Even an abnormal rapid test does not replace a properly planned sampling or the laboratory culture. When it comes to operator obligations, determining the cause, or assessing multiple pipe sections, the prescribed testing procedure is required. In a direct comparison the rapid test therefore wins the discipline "quick situational overview", not the discipline "final system assessment".
Approved sampling with laboratory culture
For the required investigation it is first determined which sampling points represent the hot water system. These can include the outlet of the domestic water heater, the circulation return and suitable more distant sampling points. Which points are actually sampled depends on the layout and use of the building. Sampling is part of the testing mandate to a testing body approved under state law; a privately taken and later submitted sample is not sufficient for this.
In the laboratory, the samples are examined using a culture method. The result is typically available after around ten days, rather than during the on-site visit. It can, however, be evaluated in the context of the documented sampling points and the system. This testing pathway is the standard for the required systemic investigation in Germany and, if carried out correctly, meets the requirements of the German Drinking Water Ordinance. Its costs, however, depend on the specific building and the scope of testing required.
Which Legionella test is right for whom?
If you're looking for an initial assessment of a particular shower in an owner-occupied household, a self-test kit may be sufficient. In a rented building where testing is legally required, that decision is already dictated by the legal requirements: an accredited testing laboratory is needed. The comparison mainly helps to avoid confusing cost and speed with informative value. The stated durations are approximate; shipping, testing procedures, and scope can change the actual process.
Comparison of three Legionella tests
Criterion | Self-test kit with laboratory submission | On-site rapid test | Approved sampling with laboratory culture |
|---|---|---|---|
Who takes the sample? | You, following the instructions | On-site professionals | An accredited testing laboratory |
Result after | About seven to ten days | Minutes to hours – fastest | Typically around ten days |
Detected Legionella | Depending on the laboratory analysis commissioned | Depending on the test; sometimes only one serogroup | Legionella in the planned culture procedure |
Informative value | Guidance for the self-sampled location | Rapid, preliminary overview of the situation | Relevant to the prescribed systemic investigation |
Legally admissible for the German mandatory inspection? | No | No | Yes, if conducted in accordance with regulations |
Approximate cost range | Usually around 50 euros – most affordable entry | Depending on the test and professional use | Depends on the property, particularly on the number of samples and the effort involved |
Suitable for | Initial orientation in private households | Quick professional pre-assessment | Mandatory inspections and comprehensive system assessment |
For landlords, property managers and businesses required to conduct testing, approved sampling is therefore the right choice. In private households, a self-test can be the first step; if an unusual value is found, a professional examination is the next sensible step. A rapid test can help speed up this process, but cannot replace it.

When is a Legionella test mandatory?
In Germany, it is not enough for a building to have "multiple apartments." According to § 31 of the Drinking Water Ordinance, several conditions must be met: The water is supplied as part of a commercial or public activity, a large-scale system for heating drinking water is present, and there are facilities that can aerosolize water, such as showers. A large-scale system is defined as, among other things, a hot water storage tank with a capacity of more than 400 liters or a pipe volume of more than three liters between the heater and the point of withdrawal; the circulation pipe is not included in this calculation. Single-family and two-family homes are exempt from this testing obligation.
Germany: What the Drinking Water Ordinance requires
For a commercial rental residential property subject to testing, the inspection must be carried out at least every three years. In the case of public activity, it is generally scheduled annually. Under certain conditions, the health department may allow a longer interval for public facilities; additional restrictions apply to facilities with particularly vulnerable people. "From three residential units" is merely a common rule of thumb, not a legal limit. The decisive factors are the actual technology, the type of water supply, and the existing points of withdrawal.
Anyone who operates a rental property should therefore consider the documentation on the hot water system together with earlier findings. The Questions and answers about Legionella testingclassify typical landlord situations. If a finding from the mandatory inspection reaches or exceeds the technical action value, the course of action is through the public health authority, investigation of the cause, and appropriate measures — not through repeated self-tests as a substitute for the finding.
That's how it is in Austria
In Austria, the German inspection requirement cannot simply be applied to residential buildings and public facilities. For the planning, operation, monitoring and refurbishment of central drinking water heating systems, Ă–NORM B 1921 is the current technical standard; it has replaced Ă–NORM B 5019 as the predecessor standard. The requirements of the current standard are differentiated according to areas of use. Therefore, you should not interpret the previously cited values of a maximum tolerable 100 KBE/100 ml or 10 KBE/100 ml in high-risk areas as blanket limit values of Ă–NORM B 1921 or as values of the Austrian Drinking Water Ordinance.
There is no general nationwide obligation to test for legionella for an ordinary private household. In facilities such as hotels, schools, nursing homes and hospitals, regular testing is important; at least annual tests are a benchmark for monitoring planning, particularly when use is sensitive. However, this does not imply a uniform legal annual requirement for each of these facilities. What is decisive are the specific system, the area of use and, where applicable, additional requirements of the respective federal state. Those in Austria who need an examination can contact an accredited laboratory or a hygiene institute.
The table categorizes typical building situations. For larger installations, it does not replace an assessment of the specific use and domestic hot water system.
Legionella testing: mandatory or voluntary?
Building | Germany | Austria |
|---|---|---|
Owner-occupied single- or two-family house | No mandatory inspection under § 31 of the Drinking Water Ordinance (TrinkwV) | No general nationwide inspection obligation for private households |
Rented multi-family building with a central large hot-water system | If all requirements are met: at least every three years | Ă–NORM B 1921 as the current technical standard (successor to Ă–NORM B 5019); check requirements based on installation and usage, no general nationwide inspection obligation as in Germany |
Hotel, school, or nursing home | If the prerequisites are met, there is an obligation to carry out examinations; for public activities, generally annually. | Regular monitoring in accordance with ÖNORM B 1921 and the area of use; at least annual tests as a basis for monitoring planning, especially for sensitive use. The previously cited 100 CFU/100 ml and 10 CFU/100 ml for high‑risk areas are not blanket limit values of the current standard; check for additional requirements. |
Whether an examination is legally required therefore depends in both countries more on the operator's role and the type of installation than on the mere desire for a quick test result.
How much does a legionella test cost?
Costs depend on the size of the building and the number of sampling points required. A self-test kit is usually sold for around 50 euros. For a legally required system inspection there is, however, no meaningful unit price: two buildings with the same number of flats can already have different pipe runs and therefore a different scope of testing. Added to this are the journey to the sampling site, the scope of the laboratory work and, if necessary, further investigations if a finding needs to be classified.
For landlords, it is also important, which Costs are incurred. The regular, required routine inspection can, under the legal and rental-contract conditions in Germany, be charged as operating costs. Costs for remedying a defect, in particular remediation and the associated re-sampling, are borne by the landlord. A written quote for the specific property makes the number of samples and scope of services comparable. The free placement service of the Fachstelle Legionellenschutz, a service of Sanquell GmbH, can support landlords in Germany in finding a suitable specialist company; the inspection itself is not free.
Who carries out a legionella test?
The sample for a mandatory German inspection is taken by a testing body that is accredited for drinking water testing and authorized under state law. It is commissioned with the examination including sampling. This means that sampling locations, procedures and documentation are part of a comprehensible assignment. Self-collected samples or an individually booked on-site test do not meet this requirement. When choosing, it is therefore worth taking a look at the proof of authorization and a written quote that clearly describes sampling, laboratory services and the number of sampling locations. Pressure to agree to an immediate, unexplained additional service is not a quality indicator.
Anyone who needs assistance with the search can use the Legionella testing for landlords ĂĽber die Legionella Protection Advisory Service contact. The private brokerage platform is a service of Sanquell GmbH and does not carry out tests itself. The request records property type, reason, location and contact details in four steps; afterwards the advisory service provides, free of charge in Germany, contacts to up to three pre-vetted specialist firms. The offer extends to all 16 federal states. For a building in Austria, an accredited laboratory or hygiene institute operating there is the appropriate point of contact instead.
Unusual finding: What to do now?
An unusual result requires orderly action, not panic. If, during a prescribed examination in Germany, the technical action value is reached or exceeded, the testing body informs the public health authority. The operator also has reporting and other obligations to act. Above all, it must be determined whether the irregularity affects a single sampling point or indicates a problem in the hot-water system. Until the cause is established, affected residents should be clearly informed about which precautions apply to them.
Interpret the result: Prüfe, an welcher Stelle die Probe entnommen wurde, wie hoch der Wert ist und welche Hinweise der Prüfbericht enthält. Ein Befund ist ein Anlass zur Ursachenklärung, keine Diagnose für Bewohner.
Inform those affected: Betreiber informieren Mieter über den Befund, mögliche Risiken und angeordnete oder empfohlene Maßnahmen. Im eigenen Haushalt sollten insbesondere Menschen mit erhöhtem Erkrankungsrisiko Bescheid wissen.
Protect in showers: Depending on the findings and professional recommendation, temporary avoidance of showering may be necessary. Tested terminal sterile filters, for example \"Legionella protection for the shower von Sanquell, physically retain Legionella directly at the point of use. The filters are tested to ASTM F838-20; a Sanquell shower filter can be installed tool-free in a few minutes and without a tradesperson. A filter does not kill the bacteria in the pipes and does not replace testing or remediation.
Have the cause investigated: A qualified person assesses the system, its mode of operation, and the findings. This includes whether temperatures, stagnation, or individual pipe sections contribute to the problem.
Repair installation: Welche technical or operational changes are required will become apparent from the inspection of the system. Cleaning individual fittings may not be sufficient in the case of a systemic problem.
Demonstrating success:After the measures, professionally planned follow-up examinations show whether they were effective. Findings, actions, and information provided to residents should be documented in a traceable manner.
How households can prevent it in everyday life
A well-operated hot water system makes it harder for Legionella to multiply. For central systems, a temperature of at least 60 °C at the storage outlet is considered an important technical reference value; adjustments to communal systems should be handled by qualified personnel. Water should not remain standing at infrequently used taps. After a long absence, run the pipes for a few minutes and avoid inhaling spray mist while doing so. Regularly cleaning and descaling showerheads is also sensible. These habits support hygiene but do not replace the required testing or the investigation of causes in the event of an abnormal finding.
Conclusion: Which Legionella test is worthwhile?
For an initial check at a tap in your own household, a self-test kit is a reasonable starting point. If a legal testing obligation must be fulfilled or a hot water system needs to be assessed reliably, there is no substitute for professionally planned sampling carried out by an accredited testing laboratory. In Germany, the Fachstelle Legionellenschutz can help connect you with suitable specialist companies. A rapid test scores points for speed but remains a preliminary assessment. In the event of an abnormal finding, point-of-use sterile filters can bridge shower use while the actual cause is investigated and remedied.
Frequently asked questions about the Legionella test
Similar questions often arise when choosing a test: Does a specialist company need to come right away, what does a rapid result tell you, and what rules apply in your local area? The answers mainly depend on whether you're looking for private guidance or are responsible for an installation subject to mandatory testing.
Can I test for Legionella myself?
Yes. With a self-test kit, you take a water sample and send it to a laboratory for analysis. The result gives you an initial indication for the sampled location. However, a self-collected sample cannot be used for a legally required examination in Germany.
How reliable is a Legionella rapid test?
A rapid test can quickly provide a preliminary overview. How much it detects depends on the test principle; some methods only Legionella pneumophilafor serogroup 1. A negative result therefore does not reliably rule out other Legionella. Proper sampling with laboratory culture remains decisive for mandatory testing in Germany.
How much does a legionella test cost?
A self-test kit usually costs around €50. For a system inspection, factors such as the building structure, the number of sampling points, travel and the extent of laboratory testing determine the price. The Legionella Protection Office, a service of Sanquell GmbH, provides contacts in Germany free of charge for a site-specific quote; the commissioned investigation is billed separately.
Who in Germany is required to have legionella testing carried out?
The obligation applies to operators who supply water from a corresponding large hot-water system in the course of a commercial or public activity and who have aerosol-generating installations. This can concern a rented multi-family building. Single- and two-family houses are exempt from the testing obligation under § 31 of the Drinking Water Ordinance (TrinkwV).
Is there a testing obligation in Austria?
For ordinary private households there is no general nationwide testing obligation. For facilities such as hotels, schools, nursing homes and hospitals, regular inspections are important; in particular, at least annual inspections may be part of monitoring plans for sensitive uses. Decisive factors are the area of use, the current Ă–NORM B 1921 and, where applicable, supplementary requirements of the respective federal state. Ă–NORM B 5019 is its superseded predecessor standard.
Where can I find a specialist company for legionella testing?
In Germany, the Fachstelle Legionellenschutz, a service of Sanquell GmbH, provides free contacts to up to three pre‑vetted specialist companies; it does not perform testing itself. When commissioning a provider, make sure that the required testing, including sample collection, is carried out by an approved testing body. In Austria you can contact accredited laboratories or hygiene institutes directly.
How can I protect myself until the result is available?
A regularly used, professionally operated hot‑water system and flushing rarely used pipes help in everyday practice. If there is a concrete suspicion or an abnormal finding, the professional recommendations for the affected showers should be followed. Point‑of‑use sterile filters tested to ASTM F838‑20, for example those from Sanquell, can retain Legionella at the tap. A Sanquell shower filter can be fitted without tools in a few minutes; it does not replace system testing or any necessary remediation.
Can you become infected with Legionella by drinking?
Drinking water is not the typical route of transmission. The critical factor is inhalation of fine water droplets, such as those produced when showering. That is why testing obligations in Germany are, among other things, based on the presence of facilities where water can be aerosolized.
At what value does it become critical?
In Germany, the technical action value is 100 CFU of Legionella per 100 milliliters. If it is reached or exceeded during a required test, the health authority is informed and measures to investigate the cause become necessary. The value is a trigger for professional action, not a blanket statement about whether an individual will become ill.
Editorial meinhaushalt.at
This guide explains test procedures and next steps for households and operators of hot water systems.